Unit
1:
(Part - A)
Main fuse board with switches
(lighting) -Distribution fuse-board with switches (lighting) -Main fuse-board
with switches (power) -Distribution fuse-board with switches (power) - Main
switches for Lighting and power. Junction of conductors-Line Existing -
Line Proposed - OH line
UG cable - Fault
UG cable - Fault
Line crossing - Socket outlet 5 amps
- Socket outlet with switch 5 amps Socket outlet 15 amps - Socket outlet with
switch 15 amps - Rewireable fuse - Cartridge fuse - Neutral link - Earth
- Bulk head fitting - Water tight fitting - Incandescent lamp - Fluorescent
Lamp Signal lamp - Push button - Bell - Fire alarm - Siren -
Storage type Water Heater - Ceiling Fan - Exhaust Fan - Energy Meter - Shielded
Cable
3 phase transformer 3 phase auto
transformer - Squirrel cage Induction Motor - Slip ring Induction Motor -
Lightning Arrester - Circuit Breaker, Isolator - Current Transformer and
Potential Transformer.
Unit
2:
(Part - B)
Rule 28 Voltage
Rule 30 Service Lines and apparatus on consumer premises.
Rule 31 Cut-out on consumer’s premises.
Rule 46 Periodical inspections and testing of consumer’s installation.
Rule 47 Testing of consumer’s installation.
Rule 54 Declared voltage of supply to consumer.
Rule 56 Sealing of meters and cut-outs.
Rule 57 Meters, maximum demand indicators and other apparatus on
consumer Premises.
Rule 77 Clearance above ground of the lowest conductor.
Rule 79 Clearance from buildings of low and medium voltage lines and
service lines.
Rule 87 Line crossing or approaching each other.
Rule 88 Guarding.
Rule 30 Service Lines and apparatus on consumer premises.
Rule 31 Cut-out on consumer’s premises.
Rule 46 Periodical inspections and testing of consumer’s installation.
Rule 47 Testing of consumer’s installation.
Rule 54 Declared voltage of supply to consumer.
Rule 56 Sealing of meters and cut-outs.
Rule 57 Meters, maximum demand indicators and other apparatus on
consumer Premises.
Rule 77 Clearance above ground of the lowest conductor.
Rule 79 Clearance from buildings of low and medium voltage lines and
service lines.
Rule 87 Line crossing or approaching each other.
Rule 88 Guarding.
Switches - Main Switches - Sockets -
Switch boards - Wall socket - Fuse units - Lamp Holders - Ceiling rose -
Distribution boxes - Miniature Circuit Breaker - Earth Leakage Circuit Breaker
- Ceiling fan - Electronic fan regulator - Storage type Water Heater –
Immersion Heater – Wires and Cables (PVC, VIR, Weather Proof) - UG Cable (LT
and HT) - Copper conductor sizes and rating – Earth wires.
Lamps: Incandescent lamp, fluorescent lamp, Sodium vapour lamp, High Pressure Mercury Vapour lamp, Halogen lamp - Neon tube/lamp - Electronic Choke for TL - Compact Fluorescent Lamp - Bus Bar Chamber - Earth plates - Stay set - Energy meter 1phase and 3 phase - Lightning Arrester - 10hp Squirrel cage Induction Motor - Electrical Fire Extinguishers – Distribution Transformer 250kVA – Current Transformer – Potential Transformer - Capacitor Bank – Star/Delta Starter.
Lamps: Incandescent lamp, fluorescent lamp, Sodium vapour lamp, High Pressure Mercury Vapour lamp, Halogen lamp - Neon tube/lamp - Electronic Choke for TL - Compact Fluorescent Lamp - Bus Bar Chamber - Earth plates - Stay set - Energy meter 1phase and 3 phase - Lightning Arrester - 10hp Squirrel cage Induction Motor - Electrical Fire Extinguishers – Distribution Transformer 250kVA – Current Transformer – Potential Transformer - Capacitor Bank – Star/Delta Starter.
Specifications of 5 KVA Single phase / three phase
alternator coupled with Diesel Engine – 62.5kVA three phase alternator with 4
stroke diesel engine.
Unit
4:
(Part - C)
Topic 1:Internal wiring, Wire size, Fuses, Shock
Wiring systems – Types of wiring – points to be considered for selection of wiring -comparison – Looping back system and Joint box system and tree system – Position of switches, cutouts, main switch board, sub-distribution boards.
Topic 1:Internal wiring, Wire size, Fuses, Shock
Wiring systems – Types of wiring – points to be considered for selection of wiring -comparison – Looping back system and Joint box system and tree system – Position of switches, cutouts, main switch board, sub-distribution boards.
Considerations for selecting wire
size – size of conductors /cable used for Domestic installation, Service
connection, Distributors - Power rating of some important house holds
electrical appliances
Materials used as fuse element –
Selection of fuse wire - types of fuses – difference between circuit breaker
and fuse – why fuse is not used in the neutral – table for sizes of fuse wire.
Electric shock – Effects of electric
shock – factors influencing the electric
shock - Precautions against electric shock – cure of shock - Treatment for electric shock - artificial respiration - fire hazards due to electricity.
shock - Precautions against electric shock – cure of shock - Treatment for electric shock - artificial respiration - fire hazards due to electricity.
Topic 2 : Earthing and Testing of Installation
Necessity – different methods – pipe earthing and plate earthing – materials required - requirements of good earth electrode – neutral wire – difference between neutral wire and earth wire - connection with earth – value of earth resistance and factors on which it is dependent – points to be remembered while providing earth – ELCB system - Earthing of domestic fitting and appliances – Industrial Earthing – Substation Earthing.
Insulation Resistance test
between earth and conductor and between conductor – Leakage test –
Insulation Resistance of motors and other equipment – Factors to be considered
for checking electrical installations – Testing of wiring installation:
introduction, verification of polarity, effectiveness of earthing, insulation
resistance, earth resistance – periodical testing – testing of UG cable –
Guidelines for installation of fitting switches, light, fans, earthing of
appliances and electrical machines.
Conditions and Requirements for
Domestic, Commercial and Industrial Installation – steps to be followed in
preparing electrical estimate (domestic, industrial and agricultural
installation)
Estimate the quantity of material
required for
- Residential single bed room Flat (1BHK).
- Industrial power wiring having 4 or 5 machines.
- School building having 3 class rooms.
- Primary Health Centre having minimum 6 rooms.
- Lighting scheme of a party hall having minimum 20 twin
TL
fittings. - Erection of one no. 15hp induction motor in Saw mill / Flour mill.
- Irrigation Pump motor (5hp) wiring.
- Computer centre having 10 computers, a/c unit, UPS, light and fan.
- Street Light service having 12 lamp light fittings
- 3 phase Service connection to a building having 5 kW
load.
Reference Books:
- Electrical Wiring, Estimating and Costing. By Dr.S.L.Uppal.Khanna Publishers.
- Electrical Design Estimating and Costing. By K.B.Raina & S.K.Battacharya. New age international (p) limited. Publishers.
Unit
1: Electrical Symbols
Need of the Electrical Symbols: Drawing is the language of engineers. For proper
communication people must use the same language so that a particular word means
the same thing to every one. In engineering drawing it is common practice to
employ graphical symbols to denote the various accessories used,=. These
symbols must convey the same meaning to everyone who reads the drawing, Symbols
are, therefore, standardized by the Bureau of Indian Standards, as far as
possible according to internationally agreed conventions as adopted by the
International Electro-technical Commission.
An important consideration in
selecting symbols is that they should be, as far as, possible, self explanatory
and easy to draw.
It must be realized that even though
the Bureau of Indian Standards has field of electrical engineering, these
symbols are not yet unversally used. Therefore, it is possible that te reader
may come across, in other books, different symbols from the one used in this
text. However, in an attempt to encourage standardization, symbols approved by
the Bureau of International Standards (ISI) have been used in this text,. The
reader is advised to make it a habit to refer to the Indian Standard
Specifications to ensure the coorectness of a symbol.
Common Electrical
Symbols:
List of Electrical Symbols
IS:2032 Gives a list of Standard symbols s given below:1.1 Kind Of Current:
1.2 System of Distribution:
1.3 Symbols of Lines:
1.4. Conductors:
Unit
2: Indian Electricity Rules (1956)
Rule 28: Voltage
Rule 30: Service Lines and apparatus on consumer premises.
Rule 31: Cut-out on consumer’s premises.
Rule 46: Periodical inspections and testing of consumer’s installation.
Rule 47: Testing of consumer’s installation.
Rule 54: Declared voltage of supply to consumer.
Rule 56: Sealing of meters and cut-outs.
Rule 57: Meters, maximum demand indicators and other apparatus on consumer Premises.
Rule 77: Clearance above ground of the lowest conductor.
Rule 79: Clearance from buildings of low and medium voltage lines and service lines.
Rule 87: Line crossing or approaching each other.
Rule 88: Guarding.
Rule 30: Service Lines and apparatus on consumer premises.
Rule 31: Cut-out on consumer’s premises.
Rule 46: Periodical inspections and testing of consumer’s installation.
Rule 47: Testing of consumer’s installation.
Rule 54: Declared voltage of supply to consumer.
Rule 56: Sealing of meters and cut-outs.
Rule 57: Meters, maximum demand indicators and other apparatus on consumer Premises.
Rule 77: Clearance above ground of the lowest conductor.
Rule 79: Clearance from buildings of low and medium voltage lines and service lines.
Rule 87: Line crossing or approaching each other.
Rule 88: Guarding.
Rule 28: Voltage:
Rule 30: Service
Lines and apparatus on consumer premises.
- The supplier shall ensure that all electric supply lines, wires, fittings and apparatus belonging to him or under his control, which are on a consumer's premises are in safe condition and in all respects fit for supplying energy and the supplier shall take due precautions to avoid danger arising on such premises from such supply lines, wires, fittings and apparatus.
- Service lines placed by the supplier on the premises of a consumer which are underground or which are accessible shall be so insulated and protected by the supplier as to be secured under all ordinary conditions against electrical, mechanical, chemical or other injury to the insulation.
- The consumer shall, as far as circumstances permit, take precautions for the safe custody of the equipment on his premises belonging to the supplier.
- The consumer shall also ensure that the installation under his control is maintained in a safe condition.
Rule 31: Cut-out on
consumer’s premises:
- The supplier shall provide a suitable cut-out in each
conductor of every service line other than an earthed or earthed neutral
conductor or the earthed external conductor of a concentric cable within a
consumer's premises, in an accessible position. Such cut-out shall be
contained within an adequately enclosed fireproof receptacle.
Where more than one consumer is supplied through a common service line, each such consumer shall be provided with an independent cut-out at the point of junction to the common service. - Every electric supply line other than the earthed or earthed neutral conductor of any system or the earthed external conductor of a concentric cable shall be protected by a suitable cut-out by its owner.
Rule 46: Periodical
inspections and testing of consumer’s installation:
(1)
(a) Where an installation is already connected to the supply system of the
supplier, every such installation shall be periodically inspected and tested at
intervals not exceeding five years either by the Inspector [or any officer
appointed to assist the Inspector] or by the supplier as may be directed by the
State Government in this behalf or in the case of installations belonging to,
or under the control of the Central Government, and] in the case of
installations in mines, oil-fields and railways, by the Central Government.
(aa)
the periodical inspection and testing of high voltage and extra high voltage
installations belonging to supplier, shall be carried out at intervals not
exceeding five years by the inspector or any officer appointed to assist the
inspector.]
(b)
where the supplier is directed by the Central or the State Government, as the
case may be, to inspect and test the installation he shall report on the
condition of the installation to the consumer concerned in a form approved by
the Inspector and shall submit a copy of such report to the Inspector 32[or
to any officer appointed to assist the Inspector and authorised under sub-rule
(2) of rule 4A].
(c)
subject to the approval of the inspector, the forms of inspection report
contained in Annexure IXA may, with such variations as the circumstances of
each case require, be used for the purposes of this sub-rule.]
(2)
(a) The fees for such inspection and test shall be determined by the Central or
the State Government, as the case may be, in the case of each class of
consumers and shall be payable by the consumer in advance.
(b) In the event of the failure of any consumer to pay the fees on or before the date specified in the fee-notice, supply to the installation of such consumer shall be liable to be disconnected under the direction of the Inspector. Such disconnection, however, shall not be made by the supplier without giving to the consumer seven clear days, notice in writing of his intention so to do.
(b) In the event of the failure of any consumer to pay the fees on or before the date specified in the fee-notice, supply to the installation of such consumer shall be liable to be disconnected under the direction of the Inspector. Such disconnection, however, shall not be made by the supplier without giving to the consumer seven clear days, notice in writing of his intention so to do.
[(c) In the event of the failure of the owner of any installation to rectify
the defects in his installation pointed out by the Inspector or by any officer
appointed to assist him and authorised under sub-rule(2) of rule 4A in the form
set out in Annexure IX and within the time indicated therein, such installation
shall be liable to be disconnected [under the directions of the
Inspector] after serving the owner of such installation with a notice:
PROVIDED
that the installation shall not be disconnected in case an appeal is made under
rule 6 and the appellate authority has stayed the orders of disconnection:
PROVIDED
FURTHER that the time indicated in the notice shall not be less than
forty-eight hours in any case:
PROVIDED
ALSO that nothing contained in this clause shall have any effect on the
application of rule 49.]
(3)
Notwithstanding the provisions of this rule, the consumer shall at all times be
solely responsible for the maintenance of this installation in such condition
as to be free from danger.
Indian
Electricity Rules
Rule 47: Testing of
consumer’s installation.
- Upon receipt of an application for a new or additional supply of energy and before connecting the supply or reconnecting the same after a period of six months, the supplier shall inspect and test the applicant's installation. The supplier shall maintain a record of test results obtained at each supply point to a consumer, in a form to be approved by the Inspector.
- If as a result of such inspection and test, the supplier is satisfied that the installation is likely to constitute danger, he shall serve on the applicant a notice in writing requiring him to make such modifications as are necessary to render the installation safe. The supplier may refuse to connect or reconnect the supply until the required modifications have been completed and he has been notified by the applicant
Rule 47A.
Installation and testing of generating units:
Where any
consumer or occupier installs a generating plant, he shall give a thirty days'
notice of his intention to commission the plant to the supplier as well as the
Inspector :
PROVIDED that no consumer or occupier shall commission his generating plant of a capacity exceeding 10KW without the approval in writing of the Inspector.]
PROVIDED that no consumer or occupier shall commission his generating plant of a capacity exceeding 10KW without the approval in writing of the Inspector.]
Rule 54. Declared
voltage of supply to consumer:
Except with the written consent of
the consumer or with the previous sanction of the State Government a supplier
shall not permit the voltage at the point of commencement of supply as defined
under rule 58 to vary from the declared
voltage-.
(i) in the case of low or medium voltage, by more than 6 per cent; or
(ii) in the case of high voltage, by more than 6 per cent on the higher side or by more than 9 per cent on the lower side; or
(iii) in the case of extra high voltage, by more than 10 per cent on the higher side or by more than 12.5 per cent on the lower side:]
PROVIDED that in the case of high voltage, the voltage variation limit of 12.5 per cent may continue till the 31st March, 1974.]
(i) in the case of low or medium voltage, by more than 6 per cent; or
(ii) in the case of high voltage, by more than 6 per cent on the higher side or by more than 9 per cent on the lower side; or
(iii) in the case of extra high voltage, by more than 10 per cent on the higher side or by more than 12.5 per cent on the lower side:]
PROVIDED that in the case of high voltage, the voltage variation limit of 12.5 per cent may continue till the 31st March, 1974.]
Rule 55. Declared
frequency of supply to consumer:
Except with the written consent of the consumer or with the previous sanction of the State Government a supplier shall not permit the frequency of an alternating current supply to vary from the declared frequency by more than 3 per cent.
Except with the written consent of the consumer or with the previous sanction of the State Government a supplier shall not permit the frequency of an alternating current supply to vary from the declared frequency by more than 3 per cent.
Rule 56. Sealing of
meters and cut-outs:
(1) A supplier may affix one or more seals to any cut-out and to any meter, maximum demand indicator, or other apparatus placed upon a consumer's premises in accordance with section 26, and no person other than the supplier shall break any such seal.
(1) A supplier may affix one or more seals to any cut-out and to any meter, maximum demand indicator, or other apparatus placed upon a consumer's premises in accordance with section 26, and no person other than the supplier shall break any such seal.
(2) The consumer
shall use all reasonable means in his power to ensure that no such seal is
broken otherwise than by the supplier.
Rule 57. Meters,
maximum demand indicators and other apparatus on consumer's premises:
(1) Any meter or maximum demand indicator or other apparatus placed upon a consumer's premises in accordance with section 26 shall be of appropriate capacity and shall be deemed to correct if its limits of error1[are within the limits specified in relevant Indian Standard Specification where no such exists, error] do not exceed 3 per cent, above or below absolute accuracy at all loads in excess of one tenth of full loads and up to full load:
[PROVIDED that for extra high voltage consumers the limit of error shall be ±1% .]
(2) No meter shall register at no load.
(3) Every supplier shall provide and maintain in proper condition such suitable apparatus as may be prescribed or approved by the Inspector for the examination, testing and regulation of meters used or intended to be used in connection with the supply of energy:
PROVIDED that the supplier may with the approval f the Inspector and shall, if required by the Inspector, enter into a joint arrangement with any other supplier for the purpose aforesaid.
(4) Every supplier shall examine, test and regulate all meters, maximum demand indicators and other apparatus for ascertaining the amount of energy supplied before their first installation at the consumer's premises and at such other intervals as may be directed by the State Government in this behalf.
(5) Every supplier shall maintain a register of meters showing the date of the last test, the error recorded at the time of the test, the limit of accuracy after adjustment and final test, the date pf installation, withdrawal, reinstallation, etc. for the examination of the Inspector or his authorised representative
(6) Where the supplier has failed to examine, test and regulate the meters and keep records thereof as aforesaid, the Inspector may cause such meters to be tested and sealed at the cost of the owner of the meters in case these are found defective.]
(1) Any meter or maximum demand indicator or other apparatus placed upon a consumer's premises in accordance with section 26 shall be of appropriate capacity and shall be deemed to correct if its limits of error1[are within the limits specified in relevant Indian Standard Specification where no such exists, error] do not exceed 3 per cent, above or below absolute accuracy at all loads in excess of one tenth of full loads and up to full load:
[PROVIDED that for extra high voltage consumers the limit of error shall be ±1% .]
(2) No meter shall register at no load.
(3) Every supplier shall provide and maintain in proper condition such suitable apparatus as may be prescribed or approved by the Inspector for the examination, testing and regulation of meters used or intended to be used in connection with the supply of energy:
PROVIDED that the supplier may with the approval f the Inspector and shall, if required by the Inspector, enter into a joint arrangement with any other supplier for the purpose aforesaid.
(4) Every supplier shall examine, test and regulate all meters, maximum demand indicators and other apparatus for ascertaining the amount of energy supplied before their first installation at the consumer's premises and at such other intervals as may be directed by the State Government in this behalf.
(5) Every supplier shall maintain a register of meters showing the date of the last test, the error recorded at the time of the test, the limit of accuracy after adjustment and final test, the date pf installation, withdrawal, reinstallation, etc. for the examination of the Inspector or his authorised representative
(6) Where the supplier has failed to examine, test and regulate the meters and keep records thereof as aforesaid, the Inspector may cause such meters to be tested and sealed at the cost of the owner of the meters in case these are found defective.]
Rule 77: Clearance
above ground of the lowest conductor:
(1) No conductor of an
overhead line, including service lines, erected across a street shall at any
part thereof be at a height less than-
(a) for low and medium voltage lines 5.8 metres
(b) for high voltage lines 6.1 metres
(a) for low and medium voltage lines 5.8 metres
(b) for high voltage lines 6.1 metres
(2) No conductor of an
overhead line, including service, lines, erected along any street shall at any
part thereof be at a height less than-
(a) for low and medium voltage lines 5.5 metres
(b) for high voltage lines 5.8 metres
(a) for low and medium voltage lines 5.5 metres
(b) for high voltage lines 5.8 metres
(3) No conductor of an
overhead line including service lines, erected else- where than along or across
any street shall be at a height less than-
(a) for low, medium and high voltage lines up to and including 11,000 volts, if bare ; 4.6 metres
(b) for low, medium and high voltage lines up to and including 11,000 volts, if insulated 4.0 metres 4.0 metres
(c) for high voltage lines above 11,000 volts 5.2 metres
(a) for low, medium and high voltage lines up to and including 11,000 volts, if bare ; 4.6 metres
(b) for low, medium and high voltage lines up to and including 11,000 volts, if insulated 4.0 metres 4.0 metres
(c) for high voltage lines above 11,000 volts 5.2 metres
(4) For extra-high
voltage lines the clearance above ground shall not be less than 5.2 metres plus
0.3 metre for every 33,000 volts or part thereof by which the voltage of the
line exceeds 33,000 volts:
PROVIDED that the minimum clearance along or across any street shall not be less than 6.1 metres.
PROVIDED that the minimum clearance along or across any street shall not be less than 6.1 metres.
Rule 79. Clearance
from buildings of low and medium voltage lines and service lines:
(1) Where a low or
medium voltage over-head line passes above or adjacent to or terminates on any
building, the following minimum clearances from any accessible point, on the
basis of maximum sag, shall be observed:-
(a) for any flat roof, open balcony, verandah roof and lean-to-roof-
(i) when the line passes above the building a vertical clearance of 2.5 metres from the highest point; and
(ii) when the line passes adjacent to the building a horizontal clearance of 1.2 metres from the nearest point, and
(b) for pitched roof-
(i) when the line passes above the building a vertical clearance of 2.5 metres immediately under the lines, and
(ii) when the line passes adjacent to the building a horizontal clearance of 1.2 metres.
(a) for any flat roof, open balcony, verandah roof and lean-to-roof-
(i) when the line passes above the building a vertical clearance of 2.5 metres from the highest point; and
(ii) when the line passes adjacent to the building a horizontal clearance of 1.2 metres from the nearest point, and
(b) for pitched roof-
(i) when the line passes above the building a vertical clearance of 2.5 metres immediately under the lines, and
(ii) when the line passes adjacent to the building a horizontal clearance of 1.2 metres.
(2) Any conductor so
situated as to have a clearance less than that specified in sub-rule (1) shall
be adequately insulated and shall be attached suitable intervals to a bare
earthed bearer wire having a breaking strength of not less than 350 kg.
(3) The horizontal
clearance shall be measured when the line is at a maximum deflection from the
vertical due to wind pressure.
[Explanation-For the purpose of this
rule, expression "building" shall be deemed to include any structure,
whether permanent or temporary .]
Rule 87:Lines
crossing or approaching each other:
(1) Where an over-head
line crosses or is in proximity to any telecommunication line, either the owner
of the over-head line or the telecommunication line, whoever lays his line
later, shall arrange to provide for protective devices or guarding arrangement,
in a manner laid down in the Code of Practice or the guideline prepared by the
Power and Telecommunication Co-ordination Commitee and subject to the
provisions of the following sub-rules.
(2) When it is intended to erect a telecommunication line or an over-head line which will cross or be in proximity to an over-head line or a telecommunication line, as the case may be, the person proposing to erect such line shall give one- month ' s notice of his intention so to do along with the relevant details of protection and drawings to the owner of the existing line.
(3) Where an over-head line crosses or is in proximity to another overhead line, guarding arrangements shall be provided so as to guard against the possibility of their coming into contact with each other. Where an over-head line crosses another over-head line, clearances shall be as under :
[Minimum clearances in metres between lines when crossing each other
(2) When it is intended to erect a telecommunication line or an over-head line which will cross or be in proximity to an over-head line or a telecommunication line, as the case may be, the person proposing to erect such line shall give one- month ' s notice of his intention so to do along with the relevant details of protection and drawings to the owner of the existing line.
(3) Where an over-head line crosses or is in proximity to another overhead line, guarding arrangements shall be provided so as to guard against the possibility of their coming into contact with each other. Where an over-head line crosses another over-head line, clearances shall be as under :
[Minimum clearances in metres between lines when crossing each other
S.No
|
Nominal
System Voltage
|
11-66
KV
|
110-132KV
|
220KV
|
400KV
|
800KV
|
1.
|
Low
and medium
|
2.44
|
3.05
|
4.58
|
5.49
|
7.94
|
2.
|
11-66
KV
|
2.44
|
3.05
|
4.58
|
5.49
|
7.94
|
3.
|
110-132KV
|
3.05
|
3.05
|
4.58
|
5.49
|
7.94
|
4.
|
220KV
|
4.58
|
4.58
|
4.58
|
5.49
|
7.94
|
5.
|
400KV
|
5.49
|
5.49
|
5.49
|
5.49
|
7.94
|
6.
|
800KV
|
7.94
|
7.94
|
7.94
|
7.94
|
7.94]
|
PROVIDED that no guardings are
required when an extra-high voltage line crosses over another extra-high
voltage, high voltage, medium or low voltage line or a road or a tram subject
to the condition that adequate clearances are provided between the lowest
conductor of the extra-high voltage line and the topmost conductor of the
overhead line crossing underneath the extra-high voltage line and the
clearances as stipulated in rule 77 from the topmost surface of the road is
maintained.]
(4) A person erecting or proposing
to erect a line which may cross or be in proximity with an existing line, may
normally provide guarding arrangements onhis own line or require the owner of
the other over-head line to provide guarding arrangements as referred to in
sub-rule (3).
(5) In all cases referred to in the
preceding sub-rules the expenses of providing the guarding arrangements or
protective devices shall be borne by the person whose line was last erected.]
(6) Where two lines cross, the crossing shall be made as nearly at right angles
as the nature of the case admits and as near the support of the lower line shall not be erected below the upper line:
(6) Where two lines cross, the crossing shall be made as nearly at right angles
as the nature of the case admits and as near the support of the lower line shall not be erected below the upper line:
[PROVIDED that the angle of crossing
of power lines shall not be less than 600.]
(7) The guarding arrangements shall
ordinarily be carried out by the owner of the
supports on which it is made and he
shall be responsible for its efficient maintenance.
(8) All work required to be done by
or under this rule shall be carried out to the satisfaction Inspector.
Rule: 88. Guarding:
(1) Where guarding is required under these rules the provisions of sub-rules (2) to (4) shall apply.
(1) Where guarding is required under these rules the provisions of sub-rules (2) to (4) shall apply.
(2) Every guard-wire shall be
connected with earth at each point at which its electrical continuity is
broken.
(3) Every guard-wire shall be an
actual breaking strength of not less than 635
(4) Every guard-wire or
cross-connected system of guard-wires, shall have sufficient current-carrying
capacity to ensure the rendering dead, without risk of fusing of the guard-wire
or wires till the contact of any live-wire has been removed.
(5) Lines crossing trolley-wires-In
the case of crossing over a trolley-wire the guarding shall fulfill the
following conditions, namely:-
(a) where there is only one trolley-wire, two guard-wires shall be erected as
in diagram A;
(b) where there are two trolley-wires and the distance between them does not
exceed 40 cms., two guard-wires shall be erected as in diagram B;
(c) where there are two trolley-wires and the distance between them exceeds
40cms. but does not exceed 1.2 metres, three guar-wires shall be erected
(d) where there are two trolley-wires and the distance between them exceeds 1.2
metres, each trolley-Wire shall be separately guarded as in diagram
(e) the rise of the trolley boom shall be so limited that if the trolley leaves
the trolley-wire, it shall not foul the guard, wires ; and
(f) where a telegraph-line is liable to fall or be blown down upon an arm, stay
-wire or span-wire, and so slide down upon a trolley-wire-, guard hooks shall
be provided to prevent such sliding.
Unit 3: Specification of Electrical Items
Switches - Main Switches - Sockets - Switch boards - Wall socket - Fuse units - Lamp Holders - Ceiling rose - Distribution boxes - Miniature Circuit Breaker - Earth Leakage Circuit Breaker - Ceiling fan - Electronic fan regulator - Storage type Water Heater – Immersion Heater – Wires and Cables (PVC, VIR, Weather Proof) - UG Cable (LT and HT) - Copper conductor sizes and rating – Earth wires.Lamps: Incandescent lamp, fluorescent lamp, Sodium vapour lamp, High Pressure Mercury Vapour lamp, Halogen lamp - Neon tube/lamp - Electronic Choke for TL - Compact Fluorescent Lamp - Bus Bar Chamber - Earth plates - Stay set - Energy meter 1phase and 3 phase - Lightning Arrester - 10hp Squirrel cage Induction Motor - Electrical Fire Extinguishers – Distribution Transformer 250kVA – Current Transformer – Potential Transformer - Capacitor Bank – Star/Delta Starter.
Specifications of 5 KVA Single phase / three phase alternator coupled with Diesel Engine – 62.5kVA three phase alternator with 4 stroke diesel engine.
thanks for ur support
ReplyDeleteThis is a very informative post! My brother is in school to become an electrical contractor. He's been struggling trying to learn all of the common electrical symbols. I can see why, there are so many to have memorized. I hope that this information will help clear up some of the things he's studying. Thanks for posting!
ReplyDeletehttp://www.bunnellelectric.com/
xI just want to thank you for sharing your information and your site or blog this is simple but nice Information I’ve ever seen i like it i learn something today. How to finish writing your book
ReplyDeleteExcellent.. Which is the first opportunity to visit this fabulous website I stumbled onto quite a few enjoyable issues and also Let me apply to ones growth about the website. Thanks Enormously Best medical marijuana dispensary
ReplyDeleteElectrical Installation Services
ReplyDeletehttp://electriciansa.co.za/
Welcome to Electriciansa, Get the emergency electrical repair and installation services in South Africa. We provide the best services for commercial electrical panel upgrades and generator wiring repairs and installations. Contact us now - 073 926 4178
Amazing content with proper examples and I like your Article thanks for shairing The Wilo Hidrainlift Waste Water Pump is designed to pump sewage from a dishwasher or washing machine. The device is capable of pumping sewage up to 60 °C. and Aflexwn is provide A Load Bank Rental & Sales can make you aware about performance of your equipment like generator, motor, etc at full load &/or partial load
ReplyDelete