Q1. Power is transmitted at high voltage
mainly to reduce:
(A)
Insulation cost
(B)
I²R losses
(C) Corona
(D)
Sag
Q2. A single-line diagram
represents a 3-phase
element by:
(A)
Three lines
(B)
A single line and symbol
(C) A circle
(D) A rectangle
Q3. Generation voltage in a power station is typically around:
(A)
11 kV
(B) 220 kV
(C)
400 kV
(D) 33 kV
Q4. Transmission voltage in India is commonly:
(A)
415 V
(B) 11 kV
(C)
220/400 kV
(D) 33 kV
Q5. Domestic single-phase supply
voltage is:
(A)
415 V
(B)
230 V
(C)
110 V
(D) 33 kV
Q6. If the transmission voltage is doubled for the same power, the line current becomes:
(A)
Double
(B)
Half
(C)
Four times
(D) Same
Q7. If current is halved, the I²R loss becomes:
(A)
Half
(B)
One-quarter
(C) Double
(D)
Same
Q8. The base load of a power system is best supplied by:
(A)
Diesel plants
(B)
Thermal/nuclear plants
(C) Gas turbines
(D)
Pumped storage
Q9 The Load factor of
the power station is the ratio of :
(A)
Peak to average
load
(B)
Average to peak load
(C)
Peak to installed
capacity
(D) Average to installed
Q10. The diversity factor
is always:
(A)
Less than 1
(B)
Greater than or equal to 1
(C)
Equal to 1
(D) Zero
Q11. A high load factor indicates:
(A)
Poor utilisation
(B)
Good/efficient utilisation of plant
(C)
Overloading
(D) Low demand
Q12. Pumped-storage plants are
used mainly for:
(A)
Base load
(B)
Peak load and energy storage
(C) Continuous supply
(D)
Reactive power
Q13. A short transmission line neglects the:
(A)
Series resistance
(B)
Shunt capacitance
(C) Series reactance
(D)
Load
Q14. A medium
transmission line lumps the:
(A)
Resistance
(B)
Shunt capacitance at ends
(C) Load
(D)
Sag
Q15. For a short
line, the ABCD constants are:
(A)
A=D=1, B=Z, C=0
(B)
A=D=0
(C) B=0, C=Z
(D)
A=Z, D=Y
Q16. For any passive
transmission line, the ABCD constants
satisfy:
(A)
A+D=1
(B)
AD-BC=1
(C) AB=CD
(D)
A=D
Q17. The unit of the B constant of a transmission line is:
(A)
Ohm
(B)
Siemens
(C) Dimensionless
(D) Volt
Q18. The unit of the C constant of a transmission line is:
(B)
ohm
(C)
Siemens (mho)
(D)
Dimensionless
(E)
Ampere
Q19. The A and D constants
of a symmetrical line are:
(A)
Different
(B)
Equal
(C) Zero
(D)
Infinite
Q20. No-load receiving-end voltage
in terms of A is:
(A)
Vs·A
(B)
Vs/A
(C) Vs·B
(D)
Vs/B
Q21. Voltage regulation of a line is the rise in receiving voltage
when:
(A)
Load is added
(B)
Full load is removed
(C) Voltage drops
(D) Frequency rises
Q22. A line with A=0.9 fed at 245 kV has a no-load
receiving voltage of:
(A)
220 kV
(B) 245 kV
(C)
272.2 kV
(D) 300 kV
Q23. The surge impedance
of a lossless line equals:
(A)
sqrt(LC)
(B)
sqrt(L/C)
(C)
LC
(D) L/C
Q24. The surge impedance
loading (SIL) of a line is the load at which:
(A)
Voltage is zero
(B)
Reactive power is balanced (flat voltage)
(C)
Current is zero
(D) Losses are max
Q25. Ferranti effect
is the rise of voltage
at the end of a long lightly-loaded line:
(A)
Sending
(B)
Receiving
(C)
Middle
(D) Neutral
Q26. The Ferranti effect
is caused by the line's:
(A)
Resistance
(B)
Shunt capacitance (charging
current)
(C)
Inductance
(D) Load
Q27. Long transmission
lines (>250 km) are analysed using:
(A) Lumped parameters
(B) Only resistance
(C) Distributed Parameter(hyperbolic functions)
(D) DC analysis
Q28. Bundled conductors are used on EHV lines mainly to reduce:
(A)
Weight
(B)
Corona and reactance
(C)
Sag
(D) Cost
Q29. Skin effect in a conductor causes the current
to concentrate:
(A)
At the centre
(B)
Near the surface
(C)
Uniformly
(D) At the ends
Q30. The proximity effect increases the of a conductor:
(A)
Capacitance
(B)
Effective resistance
(C)
Length
(D) Sag
Q31. The electric stress
in a cable is maximum
at the:
(A)
Sheath
(B)
Conductor surface
(C) Middle of insulation
(D)
Earth
Q32. The most economical
conductor radius in a cable satisfies R/r =:
(A)
1
(B)
2
(C)
e (2.718)
(D)
10
Q33. Grading of cables
is done to obtain:
(A)
Higher stress
(B)
Uniform stress distribution
(C) Lower voltage
(D)
More capacitance
Q34. In a suspension insulator string, the disc with maximum voltage is:
(A)
Nearest the tower
(B)
Nearest the line conductor
(C) In the middle
(D)
All
equal
Q35. String efficiency is 100% when the voltage
across each disc is:
(A)
Zero
(B)
Equal
(C) Maximum on one
(D)
Different
Q36. String efficiency is improved by using a:
(A)
Longer string
(B)
Grading (guard) ring
(C)
Higher voltage
(D) Smaller disc
Q37. Corona occurs when the surface
voltage gradient exceeds
about:
(A)
3 kV/cm
(B)
30 kV/cm (peak)
(C) 300 kV/cm
(D)
0.3 kV/cm
Q38. Corona loss increases with:
(A)
Larger diameter
(B)
System voltage and rough surface
(C) Wider spacing
(D)
Lower voltage
Q39. Corona can be reduced by using:
(A)
Thinner conductors
(B)
Larger diameter
/ hollow conductors
(C) Higher voltage
(D)
Closer spacing
Q40. The disruptive critical
voltage of a line is the voltage
at which:
(A)
Line melts
(B)
Corona starts
(C)
Insulation fails
(D) Sag is max
Q41. Corona has the beneficial effect of:
(A)
Increasing loss
(B)
Reducing over-voltage surges (acts as a safety
valve)
(C)
Increasing voltage
(D) Reducing spacing
Q42. The sag in a level span is given by:
(A)
wL/(8T)
(B) wL²/(8T)
(C)
wL²/(4T)
(D) 8T/(wL²)
Q43. Sag is directly proportional to the of the span:
(A)
First power
(B)
Square
(C)
Cube
(D) Square root
Q44. Sag is inversely
proportional to the
conductor:
(A)
Weight
(B)
Tension
(C)
Length
(D) Diameter
Q45. If the conductor tension is doubled, the sag becomes:
(A)
Double
(B)
Half
(C) Four times
(D) Same
Q46. The material commonly used for overhead line conductors is:
(A)
Copper only
(B)
ACSR (aluminium conductor steel reinforced)
(C)
Iron
(D) Silver
Q47. ACSR conductors use a steel core to provide:
(A)
Conductivity
(B)
Mechanical strength
(C)
Insulation
(D) Corona
Q48. Insulators for transmission lines are usually made of:
(A)
Rubber
(B)
Porcelain / glass / polymer
(C)
Copper
(D) Steel
Q49. The per-unit value of a quantity is:
(A)
Actual x base
(B)
Actual / base
(C) Actual + base
(D)
Base / actual
Q50. The base impedance
is given by:
(A)
kV²/MVA
(B)
MVA/kV²
(C) kV/MVA
(D)
MVA·kV
Q51. Per-unit impedance of a transformer is the same on:
(A)
Only HV side
(B)
Only
LV side
(C)
Both HV and LV sides
(D)
Neither side
Q52. A 0.2 pu
reactance on
100 MVA
base becomes on 50 MVA base (same kV):
(A)
0.4 pu
(B)
0.1 pu
(C) 0.2 pu
(D)
0.05 pu
Q53. The diagonal element
Yii of the Y-bus is the:
(A)
Negative of admittance
between buses
(B)
Sum of admittances connected to bus i
(C) Load at bus i
(D)
Voltage at bus i
Q54. The off-diagonal element
Yij of the Y-bus is the:
(A)
Sum at bus i
(B)
Negative of the admittance
between i and j
(C)
Load current
(D) Zero
Q55. The Y-bus matrix is generally:
(A)
Full and dense
(B)
Symmetric and sparse
(C)
Non-symmetric
(D) Diagonal only
Q56. The bus impedance matrix Z-bus is:
(A)
Same as Y-bus
(B)
Inverse of Y-bus
(C)
Transpose of Y-bus
(D) Zero
Q57. In a load-flow study, the slack bus specifies:
(A)
P and Q
(B)
V and angle
(C)
P and V
(D) Q and angle
Q58. A PV (generator) bus specifies:
(A)
P and Q
(B)
P and V magnitude
(C) V and angle
(D)
Q and angle
Q59. A PQ (load)
bus specifies:
(A)
P and Q
(B)
V and angle
(C) P and V
(D)
Q and V
Q60. The Gauss-Seidel load-flow
method is:
(A)
Fast, complex
(B)
Simple but slow convergence
(C) Non-iterative
(D)
Only for DC
Q61. The Newton-Raphson method
converges in:
(A)
Many iterations
(B)
Few iterations (quadratic convergence)
(C) One step
(D)
Never
Q62. Newton-Raphson is preferred for systems:
(A)
Small
(B)
Large
(C) DC only
(D)
Single bus
Q63. The number of iterations in Newton-Raphson is of system
size:
(A)
Strongly dependent
(B)
Nearly independent
(C) Proportional
(D) Exponential
Q64. The slack bus supplies the:
(A)
Fixed Load
(B)
System losses and balance
(C)
Reactive power only
(D)
Nothing
Q65. The primary purpose
of load-flow analysis
is to find:
(A)
Fault currents
(B)
Bus voltages and power flows
(C) Stability limit
(D)
Insulation level
Q66. A decoupled load-flow exploits the weak coupling between:
(A)
P-V and Q-angle
(B)
P-angle and Q-V
(C) V and I
(D)
R and X
Q67. Reactive power
injection at a bus generally the voltage:
(A)
Lowers
(B)
Raises
(C) Does not change
(D) Reverses
Q68. Power factor of an inductive load is improved
by connecting:
(A)
Shunt reactor
(B)
Shunt capacitor
(C)
Series resistor
(D) Series inductor
Q69. A 100 kW
load at
0.8 lagging PF needs kVAR to reach unity PF:
(A)
50
(B)
75
(C)
100
(D) 60
Q70. The capacitor kVAR for PF correction is P(tan(phi1) - tan(phi2)) where phi is the:
(A)
Voltage angle
(B)
Power-factor angle
(C)
Load angle
(D) Phase sequence
Q71. An over-excited synchronous condenser supplies
to the system:
(A)
Active power
(B)
Leading reactive power
(VARs)
(C)
DC
(D) Harmonics
Q72. On-load tap changers
control the:
(A)
Frequency
(B)
Voltage
(C)
Power factor of source
(D) Phase sequence
Q73. A shunt reactor is used to voltage on a lightly
loaded EHV line:
(A) Raise
(B)
Absorb VARs and lower
(C)
Fix frequency
(D)
Increase current
Q74. A static VAR compensator (SVC) provides:
(A)
Fixed reactive power
(B)
Fast, variable reactive
power control
(C)
Active power
(D) DC supply
Q75. Improving the power factor of a plant:
(A)
Increases line loss
(B)
Reduces line loss and frees capacity
(C)
Reduces voltage
(D) Has no effect
Q76. For economic load dispatch, all units operate
at equal:
(A)
Output power
(B)
Incremental fuel cost (lambda)
(C)
Efficiency
(D) Voltage
Q77. The incremental fuel cost is the
derivative of cost with respect
to:
(A)
Time
(B)
Power output
(C) Voltage
(D)
Current
Q78. Transmission losses are accounted for in economic
dispatch by:
(A)
Ignoring them
(B)
Penalty factors
(C) Adding fixed cost
(D)
Reducing lambda
Q79. The most economical power factor to which a load should
be corrected considers:
(A)
Only capacitor cost
(B)
Balance of capacitor cost and kVA demand saving
(C) Only demand
(D)
Zero cost
Q80. A synchronous condenser
used only for reactive power runs at:
(A)
No mechanical load
(B)
Full mechanical load
(C) Half load
(D)
Zero excitation
Q81. The reactive power (VAR) demand of a system rises when:
(A)
PF improves
(B)
Inductive load increases
(C) Voltage rises
(D) Load decreases
Q82. The main function
of a shunt capacitor bank in distribution is:
(A)
Frequency control
(B)
Power-factor and voltage
improvement
(C) Fault in meter
(D) Metering
Q83. A symmetrical (3-phase)
fault keeps the system:
(A)
Unbalanced
(B)
Balanced
(C) Open
(D)
De-energised
Q84. The most common
type of fault
is:
(A)
Three-phase
(B)
Line-to-ground (L-G)
(C) Line-to-line
(D)
Double line-to-ground
Q85. The most severe fault (highest
current) is usually
the:
(A)
L-G
(B)
L-L
(C) L-L-G
(D)
Three-phase (L-L-L)
Q86. Symmetrical components resolve an unbalanced set into balanced
sets:
(A)
Two
(B)
Three (positive, negative,
zero)
(C)
Four
(D) One
Q87. The operator 'a' in symmetrical components equals:
(A)
1 angle 90 deg
(B)
1 angle 120 deg
(C)
1 angle 180 deg
(D) 1 angle 60 deg
Q88. The sum 1 + a + a² equals:
(A)
1
(B)
0
(C)
3
(D) a
Q89. For a single line-to-ground fault, the sequence
networks are connected
in:
(A)
Parallel
(B)
Series
(C)
Delta
(D) Star
Q90. For a line-to-line fault, the positive
and negative networks
are connected in:
(A)
Series
(B)
Parallel
(C)
Series-parallel
(D) Not connected
Q91. For a double line-to-ground fault, all three sequence networks are in:
(A)
Series
(B)
Parallel
(C)
Open
(D) Delta
Q92. For
a symmetrical three-phase fault, only the sequence network is used:
(A)
Zero
(B) Negative
(C)
Positive
(D) All
Q93. Zero-sequence current can flow only if there is a path to:
(A)
Line
(B)
Ground (neutral)
(C)
Source
(D) Load
Q94. A delta winding blocks the flow of sequence
currents to the line:
(A)
Positive
(B) Negative
(C)
Zero
(D) All
Q95. The
positive-sequence impedance of a transmission line the negative-sequence impedance:
(A)
Is greater than
(B)
Equals
(C) Is less than
(D)
Is
unrelated to
Q96. The zero-sequence impedance of a line is usually the positive-sequence impedance:
(A)
Equal to
(B)
Greater than
(C) Less than
(D)
Zero
Q97. The fault current
in per unit equals:
(A)
Z_pu
(B)
1/Z_pu
(C) Z_pu²
(D)
Base MVA
Q98. The short-circuit MVA at a bus equals:
(A)
Base MVA x Z_pu
(B)
Base MVA / Z_pu
(C) 1/Base MVA
(D)
Z_pu / Base MVA
Q99. If Z_pu up to a fault is 0.25 on 100 MVA base, the fault MVA is:
(A)
25 MVA
(B)
400 MVA
(C) 100 MVA
(D)
250 MVA
Q100. The rating of a circuit
breaker is decided
by the:
(A)
Load current
(B)
Short-circuit (fault) MVA
(C)
Voltage only
(D) Frequency
Q101. A current-limiting
reactor is used to:
(B)
Limit fault current
(C)
Improve PF
(D) Reduce voltage
Q102. The making
capacity of a circuit breaker
is related to the of fault current:
(A)
RMS symmetrical
(B)
Peak (maximum asymmetrical)
(C)
Average
(D) Steady-state
Q103. The breaking capacity
of a breaker is expressed
in:
(A)
Amperes only
(B)
MVA (or kA at rated kV)
(C)
Volts
(D) Ohms
Q104. A generator's sub-transient reactance Xd'' is used for calculating the fault current:
(A)
Steady-state
(B)
Initial (first
cycle)
(C) Average
(D)
Zero
Q105. The relay that operates on excess current is the:
(A)
Differential
(B)
Over-current
(C) Distance
(D)
Buchholz
Q106. The relay that compares in and out currents of a zone is the:
(A)
Over-current
(B)
Differential
(C) Distance
(D)
Directional
Q107. The relay used mainly for transmission-line protection
is the:
(A)
Differential
(B)
Over-current
(C)
Distance (impedance)
(D)
Buchholz
Q108. A distance
relay measures the to determine
fault location:
(A)
Current only
(B)
Voltage/current ratio (impedance)
(C) Power
(D)
Frequency
Q109. The Buchholz relay is used for the protection of:
(A)
Transmission lines
(B)
Oil-filled transformers
(C) Generators
(D) Busbars
Q110. Differential protection is ideal for:
(A)
Long Lines
(B)
Transformers, generators, busbars
(C)
Feeders
(D)
Motors only
Q111. A good protection scheme must primarily be:
(A)
Slow
(B)
Selective and fast
(C) Cheap only
(D)
Manual
Q112. Back-up protection operates
when the:
(A)
Main protection succeeds
(B)
Main protection fails
(C) Load increases
(D)
Voltage rises
Q113. Neutral earthing is done to:
(A)
Increase fault current only
(B)
Limit over-voltages and provide fault path
(C) Raise voltage
(D) Reduce load
Q114. A Peterson
coil (arc-suppression coil) is a used
for earthing:
(A)
Resistor
(B)
Reactor (inductor)
(C)
Capacitor
(D) Transformer
Q115. Solid earthing
of the neutral gives earth-fault current:
(A)
Low
(B)
High
(C)
Zero
(D) Negative
Q116. Resistance earthing is used to:
(A)
Increase fault current
(B)
Limit earth-fault current
(C)
Improve PF
(D) Raise voltage
Q117. When a circuit breaker
interrupts current, the arc is formed and must be:
(A)
Increased
(B)
Quenched (extinguished)
(C)
Ignored
(D) Amplified
Q118. The breaker medium with the best arc-quenching for EHV is:
(A)
Oil
(B) Air
(C)
SF6 gas
(D) Water
Q119. A vacuum
circuit breaker is most suitable
for voltage:
(A) Extra-high
(B) Medium
(C) DC only
(D) Zero
Q120. SF6 gas is used in breakers because
it has excellent:
(A)
Conductivity
(B)
Arc-quenching and dielectric strength
(C)
Weight
(D) Colour
Q121. The restriking voltage appears across the breaker contacts:
(A)
Before opening
(B)
At the instant of arc interruption
(C)
During normal load
(D) Never
Q122. RRRV stands for:
(A)
Rate of rise of restriking voltage
(B) Rated relay voltage
(C)
Reactive rise value
(D) None
Q123. The arc in a breaker
is finally extinguished at:
(A)
Voltage peak
(B)
Current zero
(C) Current peak
(D)
Voltage zero
Q124. Auto-reclosing of breakers
is used because
most line faults
are:
(A)
Permanent
(B)
Transient (temporary)
(C) Internal
(D)
Three-phase
Q125. The purpose of a lightning arrester is to:
(A)
Increase voltage
(B)
Divert surge to earth
(C) Store energy
(D)
Improve PF
Q126. An isolator (disconnector) is operated:
(A)
On load
(B)
Off load (no current)
(C) During fault
(D)
At any time
Q127. Carrier-current protection
is a form of protection
for long lines:
(A)
Over-current
(B)
Pilot (unit)
(C) Thermal
(D)
Buchholz
Q128. The pick-up value of
a relay is the current at which it:
(A)
Resets
(B)
melts
(C) Just operates
(D) Trips instantly
Q129. Stability is the ability of a system to return to synchronism after a:
(A)
Load increase
(B)
Disturbance
(C) Voltage rise
(D)
Frequency drop
Q130. Steady-state stability concerns disturbances:
(A)
Large sudden
(B)
Small slow
(C) Zero
(D)
Fault
Q131. Transient stability concerns a disturbance such as a fault:
(A)
Small
(B)
Large sudden
(C) Slow
(D)
Steady
Q132. The swing equation
relates accelerating power to the:
(A)
Voltage
(B)
Rate of change of rotor angle
(C)
Current
(D) Frequency
Q133. In the swing equation M d²delta/dt² = Pm - Pe, M is the:
(A)
Load
(B)
Inertia constant
(C)
Resistance
(D) Reactance
Q134. The power-angle equation
is Pe =:
(A)
(EV/X) cos(delta)
(B)
(EV/X) sin(delta)
(C)
EV/X
(D) (E/V) sin(delta)
Q135. Maximum power transfer
occurs at a load angle of:
(A)
0 deg
(B) 45 deg
(C)
90 deg
(D) 180 deg
Q136. The swing curve is a plot of rotor angle versus:
(A)
Power
(B)
Time
(C)
Voltage
(D) Frequency
Q137. By the equal-area criterion, the system
is stable if:
(A)
A1
> A2
(B)
A1 = A2 is achievable
(C) No area
(D) A1 < A2 always
Q138. A1 in the equal-area criterion is the area:
(A)
Decelerating
(B)
Accelerating
(C)
Zero
(D) Load
Q139. The maximum angle for stable
fault clearing is the:
(A)
Load angle
(B)
Critical clearing
angle
(C)
Torque angle
(D) Zero angle
Q140. The time
corresponding to the critical clearing angle is the:
(A)
Fault time
(B)
Critical clearing
time
(C)
Reset time
(D) Cycle time
Q141. Faster fault clearing transient stability:
(A)
Worsens
(B)
Improves
(C) Does not affect
(D)
Reverses
Q142. Stability is improved by the transfer
reactance:
(A)
Increasing
(B)
Reducing
(C) Doubling
(D)
Ignoring
Q143. Series capacitors improve
stability by:
(A)
Increasing reactance
(B)
Reducing net line reactance
(C) Adding resistance
(D)
Raising frequency
Q144. High-speed excitation and AVR improve:
(A)
Load factor
(B)
Transient stability
(C) Corona
(D)
Sag
Q145. The steady-state stability
limit is the maximum power at delta =:
(A)
0 deg
(B)
45 deg
(C)
90 deg
(D)
180
deg
Q146. Dynamic stability includes
the effect of:
(A)
No controllers
(B)
Automatic controllers (AVR, governor)
(C)
Only faults
(D) Only load
Page 31
Q147. Loss of synchronism means the
machine’s rotor angle :
(A)
Settles
(B)
Keeps increasing without bound
(C)
Becomes zero
(D) Reverses once
Q148. A power system
stabiliser (PSS) is used to damp:
(A)
Voltage
(B)
Low-frequency oscillations
(C)
Harmonics
(D) Faults
Q149. Inertia constant H of a machine is expressed in:
(A)
Ohms
(B)
MJ/MVA (seconds)
(C)
Amperes
(D) Volts
Q150. Increasing the inertia of a machine generally transient stability:
(A)
Reduces
(B)
Improves
(C) Does not affect
(D) Reverses
No comments:
Post a Comment