100 CUSTOM PYQ-STYLE MCQs – POWER SYSTEM DISTRIBUTION
Q1. The main reason for using high voltage in distribution is:
A) To reduce copper loss
B) To increase frequency
C) To improve PF
D) To reduce corona
Ans: A
Q2. A radial distributor fed from one end has maximum voltage drop:
A) At the sending end
B) At the middle
C) At the receiving end
D) Same everywhere
Ans: C
Q3. The diversity factor of a distribution system is always:
A) Less than 1
B) Equal to 1
C) Greater than 1
D) Zero
Ans: C
Q4. In a 3-phase, 4-wire system, the neutral carries:
A) No current always
B) Sum of line currents
C) Only unbalanced current
D) Zero-sequence current only
Ans: C
Q5. Which system gives highest reliability?
A) Radial
B) Ring main
C) Interconnected
D) DC 2-wire
Ans: C
Q6. The annual load factor of a domestic consumer is generally:
A) 0.1 – 0.3
B) 0.5 – 0.6
C) 0.7 – 0.8
D) >0.9
Ans: A
Q7. The primary distribution voltage in Indian urban areas is commonly:
A) 400 V
B) 3.3 kV
C) 11 kV
D) 66 kV
Ans: C
Q8. A load curve helps to determine:
A) Maximum demand
B) Load factor
C) Plant capacity factor
D) All of the above
Ans: D
Q9. Feeder design is mainly based on:
A) Current carrying capacity
B) Voltage drop
C) Power factor
D) Loss minimization
Ans: A
Q10. Distribution transformers usually operate with:
A) Constant load
B) Overload
C) Variable load
D) No load
Ans: C
Q11. For minimum copper loss, distributors should be operated at:
A) Unity PF
B) Lagging PF
C) Leading PF
D) Zero PF
Ans: A
Q12. A customer’s maximum demand is 100 kW, annual consumption is 400 MWh. The load factor is:
A) 0.25
B) 0.45
C) 0.65
D) 0.80
Ans: B
Q13. The voltage regulation of a radial distributor is worst:
A) At balanced load
B) At power factor unity
C) At lagging PF
D) At leading PF
Ans: C
Q14. A ring distributor reduces:
A) Line losses
B) Voltage drop
C) Reliability issues
D) All of the above
Ans: D
Q15. The economy of distribution increases with:
A) Low diversity factor
B) High load factor
C) Low utilization factor
D) None
Ans: B
Q16. The unit for energy consumption is:
A) kVA
B) kVAh
C) kW
D) kWh
Ans: D
Q17. Which is true for a DC distributor?
A) No charging current
B) High corona loss
C) Less efficient
D) More insulation cost
Ans: A
Q18. Maximum demand of 500 consumers is 2 kW each. If the maximum demand on the station is 600 kW, the diversity factor is:
A) 1.0
B) 1.2
C) 1.5
D) 1.67
Ans: D
Q19. Which distribution system is simplest and cheapest?
A) Ring main
B) Radial
C) Interconnected
D) Mesh
Ans: B
Q20. Voltage regulation is best in:
A) Radial system
B) Ring main system
C) Interconnected system
D) Both B & C
Ans: D
Q21. Distribution transformer efficiency is maximum at:
A) Full load
B) ¾ load
C) Load where copper loss = iron loss
D) No load
Ans: C
Q22. The voltage unbalance in a 3-phase system should not exceed:
A) 1%
B) 2%
C) 5%
D) 10%
Ans: B
Q23. ABCD constants are mainly used for:
A) Transmission line analysis
B) Distribution feeders
C) Generator modeling
D) Load forecasting
Ans: A
Q24. The power factor of a distribution system can be improved by:
A) Shunt capacitors
B) Series inductors
C) Increasing load
D) Higher resistance conductors
Ans: A
Q25. For urban distribution, the most common system is:
A) Overhead radial
B) Underground ring main
C) Overhead mesh
D) DC 3-wire
Ans: B
Q26. The load curve plotted on a yearly basis is called:
A) Chronological curve
B) Load duration curve
C) Annual load curve
D) Demand curve
Ans: C
Q27. The “demand factor” is always:
A) Greater than 1
B) Less than 1
C) Equal to 1
D) Zero
Ans: B
Q28. A feeder in a distribution system:
A) Connects substation to distributor
B) Connects load to transformer
C) Supplies consumers directly
D) None
Ans: A
Q29. The connected load is always:
A) Less than maximum demand
B) Greater than maximum demand
C) Equal to maximum demand
D) None
Ans: B
Q30. The utilization factor is defined as:
A) kWh generated / maximum demand × hours
B) Maximum demand / connected load
C) Average load / maximum demand
D) Maximum demand / plant capacity
Ans: D
Q31. Voltage drop in AC distributors is more than DC due to:
A) Resistance
B) Reactance
C) Both R and X
D) Capacitance
Ans: C
Q32. In rural areas, distribution voltage is generally:
A) 415 V
B) 6.6 kV
C) 11 kV
D) 33 kV
Ans: C
Q33. The most economical size of conductor is obtained by:
A) Kelvin’s law
B) Ohm’s law
C) Faraday’s law
D) Lenz’s law
Ans: A
Q34. Maximum demand can be reduced by:
A) Improving power factor
B) Load shifting
C) Demand side management
D) All of the above
Ans: D
Q35. The unit of demand factor is:
A) kVA
B) kW
C) Percentage
D) Dimensionless
Ans: D
Q36. The main function of a distribution substation is:
A) Stepping up voltage
B) Stepping down voltage
C) Power generation
D) Frequency control
Ans: B
Q37. Distribution lines are designed for:
A) Constant current
B) Constant voltage
C) Constant frequency
D) Constant power
Ans: B
Q38. The voltage regulation of a good distribution system should be within:
A) ±2%
B) ±5%
C) ±10%
D) ±15%
Ans: B
Q39. Power factor correction improves:
A) Voltage profile
B) Transmission efficiency
C) Reduces losses
D) All of the above
Ans: D
Q40. A balanced 3-phase load draws:
A) Equal current in all lines
B) Zero neutral current
C) Constant power
D) All of the above
Ans: D
Q41. Which of the following is NOT a distribution system?
A) Radial
B) Ring main
C) Interconnected
D) Star-delta
Ans: D
Q42. The most economical distribution PF is:
A) 0.707
B) 0.8
C) 0.9
D) Unity
Ans: D
Q43. Peak load on a station is 100 MW, average load is 60 MW. The load factor is:
A) 0.4
B) 0.6
C) 0.75
D) 0.9
Ans: B
Q44. The reserve kept on running machines is called:
A) Cold reserve
B) Spinning reserve
C) Hot reserve
D) Operational reserve
Ans: B
Q45. For small towns, distribution is generally:
A) Underground ring
B) Overhead radial
C) Mesh
D) DC network
Ans: B
Q46. Ferranti effect is significant in:
A) Short lines
B) Medium lines
C) Long lightly loaded lines
D) DC systems
Ans: C
Q47. Reliability indices SAIFI and SAIDI are used in:
A) Power plants
B) Transmission
C) Distribution
D) Switchgear
Ans: C
Q48. A capacitor bank is connected at distribution end to:
A) Reduce PF
B) Improve PF
C) Reduce voltage
D) None
Ans: B
Q49. Losses in a distribution transformer are minimum at:
A) Full load
B) Half load
C) Load where copper = iron loss
D) No load
Ans: C
Q50. Voltage drop in a distributor depends on:
A) Load current
B) Power factor
C) Length of distributor
D) All of the above
Ans: D
Q51. The demand factor of a load is:
A) Always >1
B) Always <1
C) Always =1
D) Can be >1 or <1
Ans: B
Q52. Three-phase 4-wire supply is used for:
A) Domestic consumers
B) Large industries
C) Transmission
D) Power plants
Ans: A
Q53. Which is not an advantage of high distribution voltage?
A) Reduced current
B) Reduced copper loss
C) Reduced insulation requirement
D) Improved efficiency
Ans: C
Q54. The main cause of poor power factor in distribution is:
A) Resistive load
B) Inductive load
C) Capacitive load
D) Balanced load
Ans: B
Q55. An interconnected distribution system provides:
A) Reliability
B) Flexibility
C) Voltage stability
D) All of the above
Ans: D
Q56. The plant capacity factor is always:
A) Greater than utilization factor
B) Less than utilization factor
C) Equal to utilization factor
D) None
Ans: B
Q57. A load having maximum demand of 50 kW and average load of 25 kW has LF =
A) 25%
B) 50%
C) 75%
D) 100%
Ans: B
Q58. The peak diversity factor of a system is always:
A) <1
B) >1
C) =1
D) 0
Ans: B
Q59. In a 3-phase 4-wire system, unbalanced loads cause:
A) Zero neutral current
B) Neutral current flow
C) Reduced efficiency
D) Both B & C
Ans: D
Q60. The choice of distribution voltage depends on:
A) Amount of power
B) Distance of supply
C) Economy
D) All of the above
Ans: D
Q61. Radial system is not suitable for:
A) Short distances
B) Rural areas
C) Cities
D) Emergency supply
Ans: C
Q62. The utilization factor is:
A) Always > LF
B) Always < LF
C) Can be > or < LF
D) Equal to LF
Ans: A
Q63. The highest efficiency of distribution transformer occurs at:
A) Unity PF
B) Lagging PF
C) Leading PF
D) Independent of PF
Ans: D
Q64. A consumer uses 600 units in a month at a maximum demand of 2 kW. Load factor =
A) 0.25
B) 0.5
C) 0.75
D) 1
Ans: A
Q65. The cost of conductor material decreases with:
A) Increase in current
B) Increase in voltage
C) Decrease in voltage
D) Decrease in diversity factor
Ans: B
Q66. Which of the following is not a reliability index?
A) SAIFI
B) SAIDI
C) CAIDI
D) X/R ratio
Ans: D
Q67. The voltage profile of a distribution line can be improved by:
A) Shunt capacitors
B) Tap changing transformers
C) Series capacitors
D) All of the above
Ans: D
Q68. For the same load, copper loss is least in:
A) DC system
B) AC system
C) High voltage system
D) Low voltage system
Ans: C
Q69. If copper loss is 400 W at full load, then at half load it is:
A) 200 W
B) 100 W
C) 50 W
D) 400 W
Ans: B
Q70. Which improves load factor?
A) Peak load reduction
B) Increasing average load
C) Proper scheduling
D) All of the above
Ans: D
Q71. Which tariff encourages higher load factor?
A) Flat rate
B) Two-part tariff
C) Maximum demand tariff
D) Power factor tariff
Ans: C
Q72. The connected load is 500 kW, maximum demand 300 kW. Demand factor =
A) 0.3
B) 0.5
C) 0.6
D) 0.7
Ans: C
Q73. For the same kVA, distribution transformers are designed to have:
A) High efficiency, low regulation
B) Low efficiency, high regulation
C) Low efficiency, low regulation
D) High iron loss
Ans: A
Q74. The hourly load curve helps in determining:
A) Energy consumed
B) Load factor
C) Maximum demand
D) All of the above
Ans: D
Q75. The unit for load factor is:
A) %
B) kW
C) kVA
D) Dimensionless
Ans: D
Q76. Which one is a secondary distribution voltage?
A) 400 V
B) 11 kV
C) 33 kV
D) 66 kV
Ans: A
Q77. A balanced 3-phase load supplied by 3-phase 4-wire system has neutral current:
A) Zero
B) Maximum
C) Equal to phase current
D) Infinite
Ans: A
Q78. Which type of load is most common in distribution?
A) Resistive
B) Inductive
C) Capacitive
D) Balanced
Ans: B
Q79. Voltage drop is proportional to:
A) Current only
B) Power factor only
C) Resistance only
D) I × (R cos φ + X sin φ)
Ans: D
Q80. A system supplying small industries usually uses:
A) 3-phase 3-wire
B) 3-phase 4-wire
C) DC 3-wire
D) Single-phase 2-wire
Ans: B
Q81. In a distribution feeder, voltage is controlled by:
A) Voltage regulators
B) Shunt capacitors
C) On-load tap changers
D) All of the above
Ans: D
Q82. The annual load factor of an industrial consumer is generally:
A) 0.2 – 0.4
B) 0.5 – 0.7
C) 0.8 – 0.9
D) 0.9 – 1.0
Ans: B
Q83. The average load of a station is 30 MW, maximum demand is 60 MW. LF =
A) 0.25
B) 0.5
C) 0.75
D) 0.9
Ans: B
Q84. A 400/230 V system is a:
A) Primary distribution
B) Secondary distribution
C) Sub-transmission
D) Transmission
Ans: B
Q85. Copper loss in a distribution transformer at no load is:
A) Zero
B) Constant
C) Variable
D) Maximum
Ans: A
Q86. The phase difference between line current and voltage decides:
A) Efficiency
B) Power factor
C) Load factor
D) Diversity factor
Ans: B
Q87. The average demand divided by maximum demand is:
A) LF
B) UF
C) DF
D) PF
Ans: A
Q88. The substation which connects transmission and distribution is:
A) Primary substation
B) Secondary substation
C) Distribution substation
D) Grid substation
Ans: C
Q89. Which is not a load curve type?
A) Chronological
B) Load duration
C) Demand duration
D) Power duration
Ans: D
Q90. Higher load factor means:
A) Better utilization of plant
B) Poor economy
C) More maximum demand
D) Less energy generated
Ans: A
Q91. For better load factor, utility companies encourage:
A) Load shifting
B) Time-of-day tariff
C) PF correction
D) All of the above
Ans: D
Q92. Which is not true for ring main distribution?
A) More reliable
B) Costlier
C) Voltage regulation is better
D) Requires less conductor length than radial
Ans: D
Q93. A 200 kW load supplied at 0.8 PF draws current:
A) More than unity PF
B) Less than unity PF
C) Same as unity PF
D) Infinite
Ans: A
Q94. Shunt capacitors installed in distribution lines mainly reduce:
A) Real power loss
B) Reactive power flow
C) Voltage
D) Frequency
Ans: B
Q95. Which load curve gives information about the number of hours a load is maintained?
A) Chronological curve
B) Load duration curve
C) Maximum demand curve
D) Plant capacity curve
Ans: B
Q96. In load curve analysis, area under the curve gives:
A) Maximum demand
B) Energy consumption
C) Average load
D) Load factor
Ans: B
Q97. Power loss in lines varies with:
A) V²
B) I²R
C) cos φ
D) sin φ
Ans: B
Q98. The main limitation of radial system is:
A) High cost
B) Poor reliability
C) Complex design
D) High maintenance
Ans: B
Q99. Interconnected systems reduce:
A) Reliability
B) Reserve capacity requirement
C) Efficiency
D) Flexibility
Ans: B
Q100. A good distribution system must have:
A) Proper voltage regulation
B) High reliability
C) Low losses
D) All of the above
Ans: D